From: Debbie M. Decker <dmdecker**At_Symbol_Here**UCDAVIS.EDU>
Subject: Re: [DCHAS-L] laboratory located next to cafeteria
Date: Tue, 28 Feb 2017 19:15:25 +0000
Reply-To: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**PRINCETON.EDU>
Message-ID: BLUPR08MB5341FD561156E5C59ACCCB3C8560**At_Symbol_Here**BLUPR08MB534.namprd08.prod.outlook.com
In-Reply-To


Hi Melissa:

 

I’d be concerned not just about exhaust from the lab building being drawn into the cafeteria but food exhaust being drawn into your lab building.  I think there may be height requirements for food exhaust, too.

 

A wind tunnel study would be a good idea.  RWDI is a company we’ve worked with.  They have a variety of practice and it may be worth it to talk with them.  I have no economic interest in RWDI.

 

 

Debbie M. Decker, CCHO, ACS Fellow

Past Chair, Division of Chemical Health and Safety

University of California, Davis

(530)754-7964

(530)304-6728

dmdecker**At_Symbol_Here**ucdavis.edu

 

Birkett's hypothesis: "Any chemical reaction

that proceeds smoothly under normal conditions,

can proceed violently in the presence of an idiot."

 

 

 

From: ACS Division of Chemical Health and Safety [mailto:DCHAS-L**At_Symbol_Here**PRINCETON.EDU] On Behalf Of Melissa Ballard
Sent: Tuesday, February 28, 2017 10:47 AM
To: DCHAS-L**At_Symbol_Here**PRINCETON.EDU
Subject: [DCHAS-L] laboratory located next to cafeteria

 

I would appreciate your help again with a lab design issue. My fabulous engineering colleagues want to locate a new lab next to a cafeteria, sharing a wall. I do not like this idea. The cafeteria is a full kitchen cafeteria where it will have its own exhaust system right next to the chemical laboratory. Their solution is to have the kitchen exhaust stacks “short” and the chemical lab exhaust stacks “high” to try & eliminate the occurrence of any chemical exhaust being drawn into the kitchen intake. I have objected to this but they want a “regulation” that says they can’t do this. My professional judgment isn’t enough.

 

Any ideas?

 

 

Melissa Ballard, MSPH, CIH, CCHO

Industrial Hygienist / Industrial Hygiene Chemist

Michelin North America

1401 Antioch Church Road

IH Lab – Bldg 150 – 1st Floor

Greenville, SC 29605

Internal: 787-1843

Office: (864) 458-1843

Cell: (864) 784-9883

Fax: (864) 458-0070

email: melissa.ballard**At_Symbol_Here**michelin.com

 

D3 – Michelin Restricted

 

--- This e-mail is from DCHAS-L, the e-mail list of the ACS Division of Chemical Health and Safety. For more information about the list, contact the Divisional secretary at secretary**At_Symbol_Here**dchas.org

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.