I was assisting a customer today and just noticed in the technical drawings that the limit on the WaterSaver Faucet Co lab valves that we sell is 75 psi.  Those look like this: http://www.safetyempo rium.com/?L4200-158WSA and they are replacements for the older gas cocks that had a limit of 40 psi and look like this: http://www.safetyempor ium.com/?L2900-158WS

So, if you are using those types of valves in your system, then you obviously want to stay a few psi under those limits.

Disclaimer: those links are to my company's web site.

Rob Toreki

  =======================================================
Safety Emporium - Lab & Safety Supplies featuring brand names
you know and trust.  Visit us at http://www.SafetyEmporium.com
esales**At_Symbol_Here**safetyemporium.com  or toll-free: (866) 326-5412
Fax: (856) 553-6154, PO Box 1003, Blackwood, NJ 08012


On Jul 11, 2011, at 11:16 AM, Demer, Frank R - (demer) wrote:

Thank you all for your responses.  This is a great group!

-Frank Demer

-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Mike Hurwitz
Sent: Friday, July 08, 2011 7:11 PM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: Re: [DCHAS-L] House Air Pressure

Frank,
 We run ours at 150 PSI.  Many of the analytical instruments require
pressures between 80 and 120 PSI.  We run above that and use instrument
specific regulators.  We're also linked to the machine shop, and they
need similar pressures.

 I know that 250 PSI is a pretty standard number.  ASTM which writes the
certification procedures is tiered.  So up to a certain pressure you
fall under one certification and at higher pressures you fall under
another.  Each test is relatively expensive, so manufacturers will
certify up to whatever tier they want.  I can look, but I'm pretty sure
the first tier is at 300.

-Mike

Does anyone in the group know if there is a specific pressure limit for
laboratory house air pressure?  30 psi?

Frank R. Demer, MS, CIH, CSP
Health Safety Officer
Industrial Hygiene and Safety
University of Arizona
Department of Risk Management Services

Phone:  520.621.3585
Fax:  520.621.3706
Email:  demer**At_Symbol_Here**email.arizona.edu<mailto:demer**At_Symbol_Here**email.arizona.edu >
Mailing Address:  P.O. Box 210300, Tucson, AZ  85721-0300
Street Address:  220 W. 6th St., Tucson, AZ 85701 (2nd floor, East Bldg.)
Web Address:  risk.arizona.edu





Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.