Hi Martha and Sammye,

NFPA 55-2010 does include a provision about storing cylinders upright.  I’ve pasted it below for your convenience.

7.2.1.2 Upright Storage Flammable Gas in Solution and Liquefied Flammable Gas. Cylinders, containers, and tanks containing liquefied flammable gases and flammable gases in solution shall be positioned in the upright position.

7.2.1.2.1 Containers and Cylinders of 1.3 Gal (5 L) or Less. Containers with a capacity of 1.3 gal (5 L) or less shall be permitted to be stored in a horizontal position.

7.2.1.2.2 Containers, Cylinders, and Tanks Designed for Horizontal Use. Containers, cylinders, and tanks designed for use in a horizontal position shall be permitted to be stored in a horizontal position.

7.2.1.2.3 Palletized Containers, Cylinders, and Tanks. Containers, cylinders, and tanks, with the exception of those containing flammable liquefied compressed gases, that are palletized for transportation purposes shall be permitted to be stored in a horizontal position.

Please let me know if you have any questions about the coverage.

Best Regards,

Denise

Denise Beach
Senior Engineer 
NFPA
1 Batterymarch Park
Quincy, MA  02169-7471
Phone: 617-984-7501
Fax: 617-984-7110

From: Curtis, Martha
Sent: Wednesday, October 28, 2009 12:01 PM
To: Beach, Denise
Subject: FW: [DCHAS-L] Gas Cylinder Storage

Denise,

     Can you provide assistance on this inquiry related to NFPA 55?

  Thanks, Martha

Martha H. Curtis
Senior Chemical Specialist/Staff Liaison 
NFPA
1 Batterymarch Park
Quincy, MA  02169-7471
Phone: 617-984-7496
Fax: 617-984-7110
Email: mcurtis**At_Symbol_Here**nfpa.org

NFPA Membership keeps you Up-To-Date! Vi sit www.nfpa.org/join for more information or call 1-800-344-3555

From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**list.uvm.edu] On Behalf Of Samuella B. Sigmann
Sent: Wednesday, October 28, 2009 9:51 AM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: [DCHAS-L] Gas Cylinder Storage

On this line, are there any specific regs about lecture bottles being stored upright?  I've got a researcher that stores trace VOC gas in nitrogen lectures bottles horizontal in a cabinet.  Seems to me like all the concerns being vetted would apply, just on a smaller scale.   Any help on this out there?

Sammye

--

************************************************ ***************************************

Don’t always believe what you think.

Samuella B. Sigmann, NRCC-CHO

Lecturer/Safety Committee Chair

A. R. Smith Department of Chemistry

Appalachian State University

525 Rivers Street

Boone, NC   28608

Phone: 828 262 2755

Fax: 828 262 6558

Email: sigmannsb**At_Symbol_Here**appstate.edu

 

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.