NFPA 45 recommends 4 ACH even when the lab is not occupied. Some other ACH ranges are reported as follows:

 

OSHA 1910.1450 Appendix A Section C.4(f) Normally adequate  4-12

NFPA-45 Typical for occupied laboratories

Minimum for unoccupied laboratories 4

Typical for occupied laboratories >8

ASRAE Applications Handbook Minimum range 6-10

National Research Council Normally adequate 6-12

AIA  4-12

ANSI/AIHA Z9.5 None given

 

Richard Palluzi

PE, CSP

 

Pilot plant and laboratory consulting, safety, design, reviews, and training

www.linkedin.com/in/richardppalluzillc/

 

Richard P Palluzi LLC

72 Summit Drive

Basking Ridge, NJ 07920

rpalluzi**At_Symbol_Here**verizon.net

908-285-3782

 

From: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**Princeton.EDU> On Behalf Of Stephen Beaton
Sent: Tuesday, February 23, 2021 9:30 AM
To: DCHAS-L**At_Symbol_Here**Princeton.EDU
Subject: [DCHAS-L] Lab Ventilation

 

Good morning all:

 

A similar topic on lab ventilation came up in DCHAS a number of years back, but I would like to dig a bit further. I am interested in your thoughts and feedback, especially if any new recommendations/best practices have been made, particularly in academic laboratories.

  1. What minimum air changes per hour (ACH) do you require for the following laboratories while occupied?
    • Instructional/teaching lab
    • High risk research lab
    • Low risk research lab

Follow up – what criteria do you use to classify high risk vs low risk research labs?

  1. Do you reduce the ACH for unoccupied laboratories?
  2. Has anyone done Computational Fluid Dynamic (CFD) analysis of their typical labs to validate that the air flow rates and directions are sufficient?

I’m reviewing our current practices, and looking at adopting from ANSI Z9.5 2012 and ASHRAE TC9.10 (some familiar names as contributors).

 

Your comments are greatly appreciated.

Steve

 

 

Stephen Beaton, MSc, CHO, CRSP
Chemical Safety Manager
Environmental Health and Safety Office

DALHOUSIE UNIVERSITY
902.494.1934

 

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.