From: Richard Palluzi <rpalluzi**At_Symbol_Here**VERIZON.NET>
Subject: Re: [DCHAS-L] PNNL Hydrogen Fire Event Video
Date: Tue, 29 Jan 2019 10:15:47 -0500
Reply-To: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**PRINCETON.EDU>
Message-ID: 002101d4b7e5$833e77d0$89bb6770$**At_Symbol_Here**verizon.net
In-Reply-To


You need to be very careful as the flow limiting orifice supplied in most commercial cylinders, while limiting vs. a fully open valve, still allows an awful large flow which is more than usually required for research purposes. Installing a custom sized flow limiting restrictive orifice (available from Swagelok among others) is usually more prudent.

 

Richard Palluzi

PE, CSP

 

Pilot plant and laboratory consulting, safety, design,reviews, and training

Linkedin Profile

 

Richard P Palluzi LLC

72 Summit Drive

Basking Ridge, NJ 07920

rpalluzi**At_Symbol_Here**verizon.net

908-285-3782

 

From: ACS Division of Chemical Health and Safety <DCHAS-L**At_Symbol_Here**PRINCETON.EDU> On Behalf Of Ken Kretchman
Sent: Tuesday, January 29, 2019 8:31 AM
To: DCHAS-L**At_Symbol_Here**PRINCETON.EDU
Subject: Re: [DCHAS-L] PNNL Hydrogen Fire Event Video

 

Depending on flow rates required..obtaining flammable and/or toxic gas cylinders with flow limiting orifices is also a good practice.

 

Ken

 

 

Ken Kretchman, CIH, CSP   Director, Environmental Health and Safety

NC State University / Box 8007 / 2620 Wolf Village Way / Raleigh North Carolina 27695-8007

Email: Ken_Kretchman**At_Symbol_Here**ncsu.edu / Phone: (919).515.6860 / Fax: (919).515.6307

 

 

On Mon, Jan 28, 2019 at 10:10 PM jeskiekb**At_Symbol_Here**comcast.net <jeskiekb**At_Symbol_Here**comcast.net> wrote:

I'm going on memory from a couple of investigation updates that I've seen, but I think the answers are (1) There was heat and smoke detection in the room, not in the exhaust line for the hood. The temperature increase in the room was close to activating the sprinkler system, but did not get there. (2) They had pressure reducers in the line, but the flow into the controllers was still more than they needed. They are now looking at auto-shut-offs based on the flow rate being higher than it should be. 

 

Kim

 

Sent from my Verizon LG Smartphone

 

------ Original message------

From: Schroeder, Imke

Date: Mon, Jan 28, 2019 1:12 PM

Cc:

Subject:Re: [DCHAS-L] PNNL Hydrogen Fire Event Video

 

Thank you, Robin, for sending this around. What surprised me about the video is the absence of a fire alarm, potentially a f ire suppression system, and an automatic gas shut off for these types of experiments that could be triggered either by heat/infrared. I wonder whether that exists.

Imke

 

From: ACS Division of Chemical Health and Safety > on behalf of "Robin M. Izzo" >
Reply-To: ACS Division of Chemical Health and Safety >
Date: Monday, January 28, 2019 at 9:08 AM
To: >
Subject: [DCHAS-L] PNNL Hydrogen Fire Event Video

 

My colleague at the Princeton University Plasma Physics Lab (a DOE facility) sent me this video from the Safe Conduct of Research (SCoR) at the Pacific Northwest National Lab (PNNL).  There was a hydrogen fire and explosion in one of their fuel cell research labs in September 2018. This video highlights their incident investigation and lessons learned, and provides a good example of why it is necessary to continue to question and improve safety even for operations that have remained unchanged for many years with no serious incidents. This video is very well done and very much appreciated.

https://youtu.be/K7nf0hdHvMk

Best,

Robin

 

 

^^^^^^^^^^^^^^^^^^^^^^^^

Robin M. Izzo, M.S.

Director

Environmental Health and Safety
Princeton University

609-258-6259 (office)

609-865-7156 (mobile)

Visit the EHS website at ehs.princeton.edu and the Emergency Management website at emergency.princeton.edu

 

(she/her/hers)

 

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

--- For more information about the DCHAS-L e-mail list, contact the Divisional membership chair at membership**At_Symbol_Here**dchas.org Follow us on Twitter **At_Symbol_Here**acsdchas

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.