> >I hope you the booth is not actually in the wood shop. Flammable vapors are incompatible with combustible dusts.
>
Good point. It is in a separate room from the wood shaping area.

> >Most spray booths run only on demand since they exhaust a lot of cfm. Multiply the area of the face by a minimum velocity of 100 ft per minute. No system can afford to hurl that amount of air out the stack.

I've seen systems that do; some of our teaching labs have a similar amount of air moving through them.

Thanks for the reminder about the dust / VOC issue.

- Ralph

Ralph Stuart, CIH, CCHO
Chemical Hygiene Officer
Keene State College

ralph.stuart**At_Symbol_Here**keene.edu

---
This e-mail is from DCHAS-L, the e-mail list of the ACS Division of Chemical Health and Safety.
For more information about the list, contact the Divisional secretary at secretary**At_Symbol_Here**dchas.org

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.