From: Ralph Stuart <ras2047**At_Symbol_Here**MED.CORNELL.EDU>
Subject: [DCHAS-L] University of Hawaii lab explosion likely originated in electrostatic discharge
Date: Fri, 8 Jul 2016 10:13:33 -0400
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: 8607731990374759.WA.ras2047med.cornell.edu**At_Symbol_Here**listserv.med.cornell.edu


http://cen.acs.org/articles/94/i28/University-Hawaii-lab-explosion-likely.html

University of Hawaii lab explosion likely originated in electrostatic discharge

The root cause was failure to recognize and control the hazards of explosive gas mixture, investigation report says

By Jyllian Kemsley

The blast caused a postdoc to lose an arm and about $800,000 in lab damage.

An electrostatic discharge between postdoctoral researcher Thea Ekins-Coward and a gas storage tank containing hydrogen, oxygen, and carbon dioxide likely caused an explosion at the University of Hawaii, M€?noa, in which Ekins-Coward lost one of her arms, according to a report by the University of California Center for Laboratory Safety (UCCLS).

UH hired UCCLS to conduct an independent investigation of the March 16 accident and released the report on July 1. Another investigation by the Honolulu Fire Department, released in April, concluded that the cause was a spark from the pressure gauge. UCCLS dug deeper than the fire department and contracted with an outside laboratory to recreate and test the experimental setup. Those tests ruled out all causes other than a static discharge.

Going beyond the immediate cause of the explosion, however, ‰??the overall underlying cause of the accident was failure to recognize and control the hazards of an explosive gas mixture of hydrogen and oxygen,‰?? the UCCLS report says.

‰??The message to other researchers is that they need to do a better job of educating themselves about the hazards of the materials they‰??re working with‰?? and what could go wrong, says Craig A. Merlic, UCCLS executive director and a chemistry professor at UCLA. And campus safety personnel ‰??need to have conversations with researchers and guide them to the resources that are available‰?? to help conduct experiments safely, he adds.

In the case of the UH explosion, for example, the lab passed a safety inspection in January in part by properly storing H2 and O2 cylinders 6 meters apart. But no one questioned storing a mixture of the gases in a 49-L steel tank designed for compressed air and not electrically grounded, the UCCLS report says. When the tank exploded, it contained 55% H2, 38% O2, and 7% CO2 at a pressure of 8 atm. UCCLS estimated the energy of the detonation to be equivalent to 70.5 g of TNT.

Ekins-Coward was working for the Hawaii Natural Energy Institute under researcher Jian Yu. The gas mixture was used to feed bacteria to produce biofuels and bioplastics. Yu‰??s lab is still closed, and he and the institute have not yet determined how experiments will be set up going forward, says institute director Richard E. Rocheleau.

The explosion cost about $716,000 in infrastructure damage and $60,000 to $100,000 in equipment losses, and UCCLS was paid $88,000, says UH spokesman Dan Meisenzahl.

UH placed no restrictions on the UCCLS team during its investigation, Merlic says. The Hawaii Occupational Safety & Health Division is also examining the incident.

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.