From: Jeff Tenney <Jeff.Tenney**At_Symbol_Here**SDMYERS.COM>
Subject: Re: [DCHAS-L] plumbing H2 from remote location
Date: Thu, 1 Oct 2015 17:40:06 +0000
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: B08465628BB05D4E9F4CD5F74ACA8F1F5D269B01**At_Symbol_Here**SDMMAIL2.sdmyers.net
In-Reply-To <2E68EA190EA75E4C9399D75B40B6346679A3A73B**At_Symbol_Here**EX01.eup.edinboro.edu>


Plumbing the system to the outside is the better alternative from a safety concern. The best is a hydrogen generator, small amounts of H2 generated as needed. Safety issues are: A fire in a lab (what happens to a H2 cylinder), Moving the cylinder from the loading dock to the lab (usually involves several people handling the cylinder along with proper mounting and storage, a leaking cylinder, controlling access to the cylinder and connecting the cylinder all are safety concerns. There are some draw backs also but they have more to do with usage rather than safety like what happens when the cylinder is empty and how fast they can it be changed out but that can be addressed by correct design. An unseen leak with a piping system  will always be a concern.. Over all, a location away from people would in most causes be best with properly train personnel who handle cylinders on a regular basis. Costs are always a concern. A H2 generator may be cheaper that piping. These have been my experiences with H2 cylinders.

 

From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**med.cornell.edu] On Behalf Of Rogers, Janet
Sent: Thursday, October 01, 2015 11:25 AM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: [DCHAS-L] plumbing H2 from remote location

 

To All:

 

We need to use H2 gas for FID-GC.  Our campus EH&S officer wants us to plumb H2 gas from a cylinder placed at some remote location (as yet unknown to me, but I've heard both: a) from the hallway and b) from outside the building) to our instrument lab.  We do not see why we cannot use the H2 cylinder in the instrument lab, next to the instrument, as we have been doing.  Increasing the distance between the H2 cylinder and the instrument seems like it would increase the safety risk. 

 

I'd appreciate hearing your thoughts/comments/experience in handling H2 safely in your labs.

 

 

Janet Rogers, Ph.D.

Professor

Chemistry Department

Edinboro University of Pennsylvania

230 Scotland Road

Edinboro, PA  16444

 

phone: 814.732.1539

e-mail: rogers**At_Symbol_Here**edinboro.edu

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.