From: Wayne Wood <wayne.wood**At_Symbol_Here**MCGILL.CA>
Subject: Re: [DCHAS-L] Safety Shower Installation
Date: Wed, 11 Mar 2015 17:42:03 +0000
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: 4F21A5F3A002444D8B4F5E4B767431E572042C56**At_Symbol_Here**EXMBX2010-7.campus.MCGILL.CA
In-Reply-To


I agree with Linda.

 

In my years in EHS there were about a dozen incidents where people should have activated the emergency shower but in only 2 cases did they actually use it. When queried as to why they didn’t use the showers most people said they were afraid they would make a mess. 

 

So if you really want to increase the chances that people will actually use the shower they need to know there is a drain and, better still, they need to see it used (during testing) to have the confidence that it works. 

 

W.

 

Wayne Wood | Associate Director, University Safety (EHS), University Services –Directeur Adjoint, Direction de la prévention (SSE), Services universitaires |McGill University | 3610 rue McTavish Street, 4th floor | Montreal, Quebec, Canada, H3A 1Y2 | Tel: (514) 398-2391

 

 

 

 

 

From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU]On Behalf Of Linda E Vadura
Sent: Wednesday, March 11, 2015 12:56 PM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: Re: [DCHAS-L] Safety Shower Installation

 

Good morning,

 

Many of our newer showers/eye wash stations are without drains because of the cost. While this is considered acceptable, if not ideal, there are some behavioral repercussions.

 

People are less willing to use an emergency eye wash or shower is there is no drain. A person can think, “Is this really an emergency” - this happened in one of our teaching labs about 12 years ago. Also, lab personnel are less likely to do a routine check of an eye wash if there is no drain.

 

I recommend that if you can get drains installed, you should do so. It might save headaches in the future.

 

Linda

 

Linda Vadura

COSE Health and Safety Specialist

Campus Radiation Safety Officer

San Francisco State University

College of Science and Engineering

415.338.6892

 

 

 

 

 

On Mar 11, 2015, at 9:06 AM, Reuter,Mike - Dairy One <Mike.Reuter**At_Symbol_Here**DAIRYONE.ONMICROSOFT.COM> wrote:

 

Good afternoon,

 

Quick query.  We have a new building with labs under construction and near the final phases.  Ammonium Hydroxide (corrosive) will be used in a ventilation hood in one of the lab rooms.  There is a sink mounted eyewash planned but I just found out that no provisions were made for a safety shower.  This has now been brought to the attention of the construction group but unfortunately there is no floor drain in that lab room and it’s beyond the point where one could be installed.  The group is suggesting a location for the shower that is accessible within 5 seconds of where the chemical will be used but the individual would have to proceed through a swinging door.  Under ANSI Z358.1 a door is considered an obstruction for corrosive hazards.  Would a swinging door still be considered an obstruction?  Any advice would be great.

 

Thanks,

 

Mike

 

Michael J. Reuter

Forage Lab Chemist

Health and Safety Director

 

Dairy One

730 Warren Road

Ithaca, NY 14850

Phone: 1-607-257-1272, ext. 2166

Fax: 1-607-257-1350

 

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.