I have been told that the reason for limiting flammable is due to the difficulty of access for firefighters.
I retyped this table from IBC 2003 (Table 414.2.2). I hope it displays correctly . If it doesn’t, go to this url:
http://www2.iccsafe.org/cs/committeeArea/pdf_file/BU_06_56_07.pdf
Floor Level |
% of max allowed quantity per control area |
Number of control areas per floor |
Fire rating for control area barriers, in hours |
|
Above Grade |
Higher than 9 |
5 |
1 |
2 |
7-9 |
5 |
2 |
2 |
|
6 |
12.5 |
2 |
2 |
|
5 |
12.5 |
2 |
2 |
|
4 |
12.5 |
2 |
2 |
|
3 |
50 |
2 |
1 |
|
2 |
75 |
3 |
1 |
|
1 |
100 |
4 |
1 |
|
Below grade |
1 |
75 |
3 |
1 |
2 |
50 |
2 |
1 |
|
Lower than 2 |
Not allowed |
Not allowed |
Not allowed |
--------------------------------------------------------
Scott Goode, Professor
Department of Chemistry and Biochemistry
University of South Carolina
631 Sumter Street
Columbia SC 29208
Email: Goode**At_Symbol_Here**sc.edu
Phone: 803-777-2601
Fax: 803-777-9521
From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU]
On Behalf Of Ken Simolo
Sent: Wednesday, October 10, 2012 11:10 PM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: Re: [DCHAS-L] Advice on our new science building
For my own edification, I would appreciate someone explaining the reasoning for this code. It seems counterintuitive to me. Flammables on upper floors might be harder to fight but it seems like it is MUCH safer to the occupants of the
building to have highly flammable items at the top of the building where if they caught on fire, they would not impede flight from the building nor would they start to catch the floors above them on fire. I can not imagine that they are worried about flammable
liquids dripping below. Even if they did a little bit, it seems like that would be much less of a risk. Think of the twin towers - the people above the impact were trapped by the fire, not the people below.
Thanks,
Ken
On Oct 10, 2012, at 6:47 PM, GOODE, SCOTT wrote:
I would look very hard at the decision to put the chemists on the upper floor. In South Carolina, state buildings, like those of my university are governed
by the International Building Code (IBC). and I don’t have the current code (IBC 2012) , but the last campus lab building we constructed was under IBC 2003 and I don’t think there are changes.
The problem is solvent storage. You are allowed 4 control areas (1-hr fire barriers) on the first floor, each with 30 gal of flammable liquids. You can add
100% if the flammables are stored in a fire-rated cabinet and 100% if the area is sprinklered, so the maximum is 120 gal per control area.
On the 4th floor, you are allowed a maximum of two control areas, each with 12.5% of the quantity allowed
for a first floor control area. That means a total of 30 gal of solvent on a fourth floor, 15 per control area if sprinklered and stored in solvent cabinets.
Scott Goode
--------------------------------------------------------
Scott Goode, Professor
Department of Chemistry and Biochemistry
University of South Carolina
631 Sumter Street
Columbia SC 29208
Phone: 803-777-2601
Fax: 803-777-9521
From: DCHAS-L
Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU] On Behalf Of Richardson, Nancy A
Sent: Monday, October 08, 2012 2:35 PM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: [DCHAS-L] Advice on our new science building
We are building a new building that will house health sciences, physics, biology, and chemistry. It will be mainly a teaching building with classrooms, teaching labs and
faculty office areas. We may have a few small research areas here and there. We chemists will have the top(fourth) floor for our 6-8 teaching labs, chemical storage, and office area along with one or two small seminar/meeting rooms for around 24 people.
I teach as well as do safety and so I am trying to give the best safety advice in the design as I can, but feel rather inadequate for the task. I wonder if others have some advice to offer. As we design the layouts for the rooms, certain particular questions
have arisen and I was wondering what others’ experiences have been with some of the following aspects or other aspects that have not surfaced yet:
1. Are
ductless hoods a reasonable choice for some/all teaching labs? I am most concerned with the great variety of materials that the organic labs use. They tend to do different experiments every time through the course and I think it might be hard to ensure the
filters were always adequate. Also, other teaching labs get used for research(that uses all different materials) from time to time when lab classes are not meeting. What opinion could any of you offer on ductless hoods? Are they ultimately cost effective?
Are they maintenance intensive?
2. In
planning teaching labs, there is a question as to whether all the students in a lab need to be under a hood for distillations of various types or working with other materials such as silica. The introductory chemistry class lab distills mouth wash in one
experiment. Does the ethanol concentration in the air pose any actual risk or the menthol? Is there some law that says exactly what should be done under a hood? Could hexane, methylene chloride, and ether be outside of a hood, for example, with enough general
room ventilation and how could these be monitored to ensure safe levels in the listed standards for some chemicals? The appendix in 1910.1450 suggests 2.5 ft person for hood space, but is this done in teaching lab design when one setup is shared by two or
maybe four students? Would hood bonnets be a good alternative for some things?
3. Are
there some chemically resistant AV projectors that could be placed into labs. We had wanted projectors in labs before, but since other metal(locks, fume hoods, the safety shower) in the labs had become corroded it was thought that projectors would not stand
up to chemical exposure? Or with a good ventilation design will this not be an issue?
4. What
about storing materials in labs? Now we have a good bit of storage within the teaching labs in our old building because there is no other place for it, but from what I can tell, there are limits on in lab storage of flammables even if there are flammable
cabinets.
5. What
is the practice with regard to receiving chemicals and transporting them to upper floors? I am especially concerned about gas cylinders.
Thank you in advance for any opinions and experience anyone has on these topics and with these issues and perhaps other building design issues.
Nancy