From: "Wright, Mike" <mwright**At_Symbol_Here**USW.ORG>
Subject: Re: [DCHAS-L] 40 Micron aluminum powder
Date: February 28, 2012 5:33:44 PM EST
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: <024501ccf65e$2f7be830$8e73b890$**At_Symbol_Here**com>


Getting it real wet is fine. It eliminates the dust. But don't let it get moist but airborne. That increases the risk, by generating hydrogen.

 

Michael J. Wright

Director of Health, Safety and Environment

United Steelworkers

5 Gateway Center

Pittsburgh, PA 15222

 

Work (412) 562-2580

Cell     (412) 370-0105

Fax     (412) 562-2584

 

mwright**At_Symbol_Here**usw.org

 

Visit us on the web at www.usw.org

 

From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU]On Behalf Of NEAL LANGERMAN
Sent: Tuesday, February 28, 2012 4:16 PM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: Re: [DCHAS-L] 40 Micron aluminum powder

 

If possible, wet wipe the powder.  This reduces the flammability and gets around the problem.  Water or water plus a detergent is fine.  If critical cleaning is needed and I doubt that it is, follow the water with an IPA wipe down but watch out for exceeding VOC release regulations.

 

Alternatively, the PI will need to foot the bill for the correct dust removal and capture system and the cleaning operations costs.

 

 

------------------------------------------------------------------------------------

The information contained in this message is privileged and confidential and protected from disclosure. If the reader of this message is not the intended recipient, or an employee or agent responsible for delivering this message to the intended recipient, you are hereby notified that any dissemination, distribution or copying of this communication is strictly prohibited. If you have received this communication in error, please notify us immediately by replying to the message and deleting it from your computer.

 

ACSafety has a new address:

NEAL LANGERMAN, Ph.D.

ADVANCED CHEMICAL SAFETY, Inc.

PO Box 152329

SAN DIEGO CA 92195

011(619) 990-4908 (phone, 24/7)

www.chemical-safety.com

 

We no longer support FAX.

 

 Please contact me before sending any packages or courier delivery.  The address for those items is:

5340 Caminito Cachorro

San Diego CA 92105

 

From: DCHAS-L Discussion List[mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU]On Behalf Of Don Abramowitz
Sent: Tuesday, February 28, 2012 12:34 PM
To: DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject: Re: [DCHAS-L] 40 Micron aluminum powder

 

If you are interested in a vacuum cleaner, you might want to talk to the folks at Nilfisk.  From their "Combustible Dust FAQs" page:  " In short, just because your facility handles combustible dust does not mean you need an explosion-proof vacuum�but you might."  This FAQ page,http://explosionproof-vacuum.com/explosion-proof-vacuum-faq.html, takes you to some other resources, and it might well be worth a call to their tech support staff.

                              Don

Donald Abramowitz
Environmental Health & Safety Officer
Bryn Mawr College
101 N. Merion Avenue
Bryn Mawr, PA 19010-2899
(610) 526-5166

 


Dear DCHAS members:

One of PI in our campus is using 40 micron aluminum powder for the research purpose. After experiment/manipulations, they generate dust (fine layer of Al dust) in the room as well as in instrument surfaces. According from F1 Sheet from the Aluminum Association specified "Standard commercial industrial vacuum cleaners must not be used during cleaning. Vacuum cleaning systems, designed and certified for use withGroup E combustible dusts may be used, with limitations (see NFPA 484)".Aluminum powder is highly flammable and can explode in the air under circumstances. [MSDS (JT Baker):Flammable solid, dust may form flammable or explosive mixture with air. Nanomaterial Store MSDS: contact with water liberates extremely flammable gases, spontaneously flammable in air.]

According to NFPA 484: 8.1.2.3.4: When being used for aluminum powders and aluminum dust, portable vacuum cleaners shall be used only if listed or approved for use with group E dusts (combustible aluminum dust) and shall be identified for use with aluminum only.

I need your recommendations/suggestions in respect to cleaning/decontamination procedures used for the fine layer of materials. Please let me know if any of your facility is working with similar conditions with the aluminum dust. I will greatly appreciate your help in this matter.

Best Regards,

Tilak

Tilak Chandra, Ph.D.
Chemical Safety Specialist
Environment, Health and Safety
University of Wisconsin-Madison
30 East Campus Mall
Madison, WI 53715
Ph. 608-890-0255
FAX 608-262-6767
tchandra**At_Symbol_Here**fpm.wisc.edu

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.