Dan,

Much appreciated. . .

Thank You!


Angelo T. Chinni, CIH, CSP
Mail Drop Code 4914                        Phone: 317-277 8390
Lilly Corporate Center -LTC              Fax:       317-651-6937
Indianapolis, IN 46285                     Mobile: 317-730-0924
E-Mail: Chinniat**At_Symbol_Here**lilly.com              



"Shiel, Dan" <dan.shiel**At_Symbol_Here**PFIZER.COM>
Sent by: DCHAS-L Discussion List <dchas-l**At_Symbol_Here**MED.CORNELL.EDU>

10/28/2011 12:46 PM
Please respond to
DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>

To
DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
cc
Subject
Re: [DCHAS-L] GFCI's and requirements for locating near safety showers, and/or Sinks. . .





Hi Angelo:
 
Here are a few excerptsfrom NFPA that should help:
 
NFPA 70, Article 210 requires GFCIs in these locations (I left out items (1)-(4) as they are not applicable to  labs):
 
(5) Sinks — where receptacles are installed within1.8 m
(6 ft) of the outside edge of the sink.
Exception No. 1 to (5): In industrial laboratories, receptacles
used to supply equipment where removal of power
would introduce a greater hazard shall be permitted to be
installed without GFCI protection.
Exception No. 2 to (5): For receptacles located in patient
bed locations of general care or critical care areas of
health care facilities other than those covered under
210.8(B)(1), GFCI protection shall not be required.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas where electrical
diagnostic equipment, electrical hand tools, or portable
lighting equipment are to be used
 
 
 
NFPA 45 has the following regarding fume hood electrical devices:
 
8.8.4* Electrical Devices.
8.8.4.1 In installations where services and controls are within
the hood, additional electrical disconnects shall be located
within 15m(50 ft) of the hood and shall be accessible and clearly
marked.
8.8.4.2 If electrical receptacles are located external to the
hood, no additional electrical disconnect shall be required.
(See 5.6.1.)
 
 
Regards,
 
Dan
 
Dan Shiel, MBA, CSP, CHMM
Director, Risk & Quality Management Services
Pfizer La Jolla/ GO R&D West
10777 Science Center Drive
San Diego, CA 92121
 
“Money is the most envied, but the least enjoyed.
Health is the most enjoyed, but the least envied.”

Charles Caleb Colton,1780-1832, British sportsman writer

 
 
 
From: DCHAS-L Discussion List [mailto:dchas-l**At_Symbol_Here**MED.CORNELL.EDU] On Behalf Of Angelo T Chinni
Sent:
Thursday, October 27, 2011 9:50 AM
To:
DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU
Subject:
[DCHAS-L] GFCI's and requirements for locating near safety showers, and/or Sinks. . .

 

All,


(Please forgive me if this is a repeat question. . .)


I am sending a request to the group for assistance in locating any U.S.  regulations, design standards, codes with regard to providing Ground Fault Circuit Interuptor  (GFCI) protection (in Laboratories) for electrical outlets located within the vicinity of eyewashes, and/or sinks.  Additionally, are laboratory fume hoods (with water and drains supplied) provided with such protection (in addition to emergency power shut-off switches).  


I would appreciate hearing from this group's experience.


Any history, background or references would be much appreciated.  Please reply directly to chinniat**At_Symbol_Here**lilly.com


Thanks.



Angelo






Angelo T. Chinni, CIH, CSP
Mail Drop Code 4914                        Phone: 317-277 8390
Lilly Corporate Center -LTC              Fax:       317-651-6937
Indianapolis, IN 46285                     Mobile: 317-730-0924
E-Mail: Chinniat**At_Symbol_Here**lilly.com              

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.