Subject: Re: Sprinkler System in Wet Chemistry Research Labs
In-Reply-To: <390C703D90CE97409F79127132E33D341F6074676F**At_Symbol_Here**usto-pmsg-mbs05.am.corp.amgen.com>

John, I cannot speak to NFPA requirements on flammable liquid use in chemic
al fume hoods, but...

I can say that NFPA Codes/Standards do indicate sprinklers in gas cabinets 
+ exhaust ducting for pyrophoric gas use and/or semiconductor research / ma
nufacturing.  See NFPA 45 and NFPA 318, respectively.  I also see mention o
f sprinklers in paint booths and associated exhaust systems.  Perhaps the i
nsurer views the hoods you mention as analogous to paint booth operations? 
 Alternatively, if these hoods are more storage than operations, then the a
nalogy is drawn to inside liquid storage room per NFPA 30.

Whatever the case, I'd ask the insurer to cite you chapter and verse for re
commendations for upgrades.

All the best,
-Nick
___________________________________
Nicholas J.=A0Tsiakals
Division of Research Safety
Chemical Safety Section
University of Illinois at Urbana-Champaign
(217) 244 - 0682
www.drs.illinois.edu
=A0
"If we don't train students in risk management and safety procedures, then 
we're not training them for employment in modern industry.=A0 If we want so
meone to turn up in a job and be productive, they can't do that if they're 
not safety aware."=A0 
=A0=A0=A0 -- Prof. Thomas Welton, Head, Department of Chemistry, Imperial C
ollege London --


-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Ar
vedson, Steve
Sent: Tuesday, May 18, 2010 1:53 PM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: Re: [DCHAS-L] Sprinkler System in Wet Chemistry Research Labs

We use a water-mist system in our larger hoods (floor-mounted and scale-up)
.  The system was provided by Marioff, now part of United Technologies Corp
 (UTC) (http://www.hi-fog.com).  The advantages are that it minimizes damag
e to equipment (including electronics) in the hoods, minimizes smoke damage
, and extinguishes the fire very quickly.  It is more effective than regula
r sprinklers at extinguishing flammable and combustible liquid fires.  The 
chemists accept it because the total volume of water is small and there isn
't water raining down on their equipment and chemicals.

Steve Arvedson
Senior Manager, Research Operations
Chemistry Research & Discovery
Amgen Inc.
One Amgen Center Drive
Mail Stop 29-2-C
Thousand Oaks, CA 91320-1799

-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Jo
hn_Bristol**At_Symbol_Here**EISAI.COM
Sent: Tuesday, May 18, 2010 10:22 AM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: Re: [DCHAS-L] Sprinkler System in Wet Chemistry Research Labs

While on the topic of sprinkler systems, what is everyone's view on
sprinkler systems installed inside a fume hood?  This has been a topic that
our insurer has batted around with us for years.  They would like to
recommend sprinklers be installed inside fume hoods where larger volumes of
flammable solvents are used (such as floor-to-ceiling fume hoods in our
scale-up labs and waste accumulation rooms).

Any comments would be appreciated.

Thanks,
John

John Bristol
Director, Environmental Health and Safety
Andover Site Operations Unit
Eisai Inc.
Four Corporate Drive
Andover, MA  01810


                                                                           
                                              
  From:       "House, Katherine C."                 
                                              
                                                                           
                                              
  To:         DCHAS-L**At_Symbol_Here**LIST.UVM.EDU                                         
                                              
                                                                           
                                              
  Date:       05/18/2010 01:13 PM                                          
                                              
                                                                           
                                              
  Subject:    Re: [DCHAS-L] Sprinkler System in Wet Chemistry Research Labs
                                              
                                                                           
                                              
  Sent by:    DCHAS-L Discussion List                
                                              
                                                                           
                                              



We use these folks for our entire plant.  I'm not sure if Knoxville is in
his territory, but I'm sure he would send you in the right direction.
Billy Cole
SimplexGrinnell LP
(919) 279-6400
(919) 219-4850
I would also recommend these folks; again I'm not sure if Knoxville is in
her area, but I'm sure she'd make a referal.
Erin O'Kelley
ADT Security
(919) 388-5482
eokelley**At_Symbol_Here**adt.com
Either way, I'd check with your facilities folks to see which vendors are
used in other parts of the university.  You might get better service this
way and it's definitely easier to work with only one vendor.  If they don't
have someone they recommend, you want to make sure you find a vendor that
understand the safety needs of a laboratory.
Cheers,

Katherine C. House, CCHO
Laboratory Coordinator
Chemical Hygiene Officer
Cormetech, Inc.
5000 International Drive
Durham, NC 27712
919.620.3044 (office)
919.815.2024 (mobile)

-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**list.uvm.edu] On Behalf Of
paracelcusbombastusvon**At_Symbol_Here**juno.com
Sent: Tuesday, May 18, 2010 8:59 AM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: Re: [DCHAS-L] Sprinkler System in Wet Chemistry Research Labs

Contact a local sprinkler design and engineering or fire engineering
consultant in addition to your insurer.
Lynn Knudtson

---------- Original Message ----------
From: Al Hazari 
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: [DCHAS-L] Sprinkler System in Wet Chemistry Research Labs
Date: Mon, 17 May 2010 15:19:13 -0400

The University of Tennessee, Knoxville is renovating three biology labs
to be used Wet Chemistry Research Labs. Any recommendations for a
sprinkler system in the new labs ?  Thanks.    Al Hazari

____________________________________________________________
Refi - Low as 3.38% APR
Homeowners: Refi before rates rise. $300k for $1,306/mo. No SSN req'd
http://thirdpartyoffers.juno.com/TGL3131/4bf28f4a6439e572434st05vuc






                            *****Eisai Disclaimer*****

This e-mail message may contain privileged, confidential and/or proprietary
information of Eisai.   If you believe that it has been sent to you in
error, please contact the sender immediately and delete the message
including any attachments, without copying, using, or distributing any of
the information contained therein. This e-mail message should not be
interpreted to include a digital or electronic signature that can be used
to authenticate an agreement, contract or other legal document, nor to
reflect an intention to be bound to any legally-binding agreement or
contract.

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.