Subject: Re: flammability class vs NFPA number
Comments: cc: Sammye Sigmann
In-Reply-To: A

The correlation between the NFPA 704 Flammability Hazard Rating and the NFPA 30 flammable/combustible liquid Class designation can be found in NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response.

Class IA liquids are NFPA 704 Flammability Rating 4.
Classes IB and IC liquids are NFPA 704 Flammability Rating 3.
Classes II and IIIA liquids are NFPA 704 Flammability Rating 2.
Class IIIB liquids are NFPA 704 Flammability Rating 1.

You can view (but cannot copy) NFPA 704 by going to the following web page:

http://www.nfpa.org/aboutthecodes/list_of_codes_and_standards.asp

Scroll down to and select the desired document.  Scroll to the bottom of the next screen and select "Preview this document".  Follow the instructions.  Because the "on-line" documents are located on an external server, expect system loading and response to take some time.
---------------------------------------------------------------------------------------------------------
Robert P. Benedetti, CSP, PE
Principal Flammable Liquids Engineer
National Fire Protection Association
1 Batterymarch Park
Quincy, MA  02169-7471
617-984-7433
617-984-7110  (FAX)
617-571-8494  (CELL)
bbenedetti**At_Symbol_Here**nfpa.org

NFPA Membership keeps you up-to-date!
Visit www.nfpa.org/join for more information.  Or call 800-344-3555.

********************************
Notice:  The information contained in this electronic message and any attachments to this message are intended for the exclusive use of the addressee(s) and may contain confidential and/or privileged information.  If you are not the intended recipient, please notify Robert Benedetti immediately by replying to the message or by calling (617) 984-7433.  Please delete this message and any attachments from your system.  Thank you.

-----Original Message-----
From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Sammye Sigmann
Sent: Monday, March 03, 2008 10:44 AM
To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU
Subject: [DCHAS-L] flammability class vs NFPA number

Can anyone tell me how the number assigned in the NFPA diamond for 
flammability corralates (if it does) with the flammability class of the solvent?  
That is, are all "4"s on the diamond solvents that are in Class IA & IB, etc.  I 
do not have the code books, and so far have not been able to locate this info 
on the web.

Thanks in advance for any wisdom,
Sammye

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.