I agree. Several years ago I learned that gas mixtures are regulated based on the properties of the mixture as a whole. For example, pure fluorine would be treated as a highly toxic gas and would be required to be stored in a ventilated gas cabinet, whereas, fluorine mixtures of 100 ppm to 10% in argon, nitrogen, or helium would not. I would assume this applies to water soluble mixtures as well. Chris -----Original Message----- From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of Erika Sent: Tuesday, January 30, 2007 9:01 AM To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU Subject: Re: [DCHAS-L] Aqueous/Flammable solvent mixtures While I agree with Carl that flammable solvent mixtures are generally judged by their flash point, I disagree with the blanket statement that "All flammable solvents mixed with water should be treated, handled, and stored as flammable liquids." If a flammable solvent is completely miscible with water, said solution is used a dilution which yields no flash point, and the solution will not sustain combustion in a fire (i.e., has no "fire point"), no regulation or insurer is going to be concerned with their storage (or shipment) as a flammable liquid. The basic problem (to which Susan Hadden alludes) is generating the data for any such solution. Perhaps somebody has done this, but I am not aware of any published data. Richard Rosera Environmental Specialist Reckitt Benckiser, Inc. Hillsborough, NJ ----- Original Message ----- From: "Carl Zipfel" To: Sent: Monday, January 29, 2007 6:38 PM Subject: Re: [DCHAS-L] Aqueous/Flammable solvent mixtures > I went down this road many years ago and gave up. The problem is that the > only acceptable test of flammability is the "flash point". The flash point > defines flammability, and is what is accepted by the EPA, OSHA, and more > importantly the insurance companies. While the solvents that you mention > are miscible, once a little heat is applied they will separate and form a > flammable mixture in the air. All flammable solvents mixed with water should > be treated, handled, and stored as flammable liquids. > > Carl Zipfel, csp > > > ----- Original Message ----- > From: "Hadden, Susan [PRDUS]" > To: > Sent: Monday, January 29, 2007 2:36 PM > Subject: [DCHAS-L] Aqueous/Flammable solvent mixtures > > > > Many of our researchers use aqueous mixtures of miscible flammable > solvents > > for their LC work. They often have questions about storage and whether to > > treat them as flammable or not. I've been looking for data that might show > > me flammability as a function of concentration for the common solvents > such > > as CH3CN, MeOH, EtOH, IPA, etc. I've checked OSHA, NFPA and ASTM but can't > > find any solvent specific data. Does anyone know where I might find that > > information? > > > > Thanks, > > > > Susan Hadden > > Senior Occupational Safety Specialist > > J&J PRD Environmental, Health & Safety > > 1000 Rt 202, PO Box 300 > > Raritan, NJ 08869 > > 908-704-4295 (ph), 908-707-9211 (fax) >

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.
The maintenance and hosting of the DCHAS-L archive is provided through the generous support of Safety Emporium.