Date: Fri, 14 Jul 2006 17:04:09 -0400
Reply-To: chemcon**At_Symbol_Here**JUNO.COM
Sender: DCHAS-L Discussion List <DCHAS-L**At_Symbol_Here**LIST.UVM.EDU>
From: Jay Young <chemcon**At_Symbol_Here**JUNO.COM>
Subject: Re: Fume hood sashes
Comments: To: rstuart**At_Symbol_Here**UVM.EDU
Ralph,

Removing that air foil is a bad, unsafe idea.  The purpose of the air
foil is to enhance non-turbulent air flow into the hood.  When the air
flow into a hood is turbulent, some fraction, which could be as large as
80 or 90%, or greater, of the toxic fumes and gases that should have
exited out through the venting of the hood now, with turbulence, enter
the room where people are working and breathing the toxic contaminated
air.

Hoods from which those air foils have been removed should NEVER be used
as fume hoods until the air foils are replaced and the hood re-tested to
be sure it is in compliance with the manufacturer's and installer's
specifications.

Jay Young

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.