Dear Ms. Marcoux:

NFPA 45-2004, Standard on Fire Protection for Laboratories Using
Chemicals, reads as follows on the topic:

9.2.3.5*  Storage cabinets used in laboratories shall not be required to
be vented for fire protection purposes.

A.9.2.3.5  See NFPA 30, Flammable and Combustible Liquids Code, for
performance-based requirements if storage cabinets are vented for any
reason.

 

I would suggest you review a copy of NFPA 30.  If you don't have access
to a copy of NFPA 30 through your health and safety personnel or fire
marshal, you can order an instantly downloadable .pdf of NFPA 30 through
our website at www.nfpa.org  .  I hope this will
give you another source for information.

Amy Spencer

NFPA Senior Chemical Engineer/Staff Liaison to NFPA 45

 

-----Original Message-----
From: Curtis, Martha 
Sent: Wednesday, June 01, 2005 3:59 PM
To: Spencer, Amy
Cc: Benedetti, Bob
Subject: FW: [DCHAS-L] quick question

 

Amy,

     Can you provide any assistance from NFPA 45 to the inquiry from the
ACS, Division of Chemical Health and Safety list?

  Regards, Martha

 

Martha H. Curtis

Senior Fire Service Specialist/Staff Liaison

NFPA

1 Batterymarch Park

Quincy, MA  02169-7471

Phone: 617-984-7496

Fax: 617-984-7056

Email: mcurtis**At_Symbol_Here**nfpa.org

 

NFPA's mission is to reduce the worldwide burden of fire and other
hazards on the quality of life by providing and advocating
scientifically-based consensus codes and standards, research, training
and education.

 

-----Original Message-----

From: DCHAS-L Discussion List [mailto:DCHAS-L**At_Symbol_Here**LIST.UVM.EDU] On Behalf Of
Megan.Marcoux

Sent: Wednesday, June 01, 2005 11:09 AM

To: DCHAS-L**At_Symbol_Here**LIST.UVM.EDU

Subject: Re: [DCHAS-L] quick question

 

Hello there,

  I have been passed on to this address with my question I hope that
someone will be able to help me. My question is...here at CMCC in the
prep room of the chemistry lab there is a storage closet with no
ventillation and several cabinets in this location. The cabinet of
concern is a acid cabinet, the only ventillation it has is the two air
vents on either side. We are looking to replace the cabinet and possibly
incorporating ventillation through the ceiling up above for this
cabinet. Our question is where can I find information(or the answer) on
regulations for the proper setup of a ventillation system for that
storage room so that it doesn't interfere with the fume hood system and
HVAC? I do hope you can help, if not please let me know and where my
next lead would be. Thank you for your time.

 

Megan Marcoux

intern at CMCC

Previous post   |  Top of Page   |   Next post



The content of this page reflects the personal opinion(s) of the author(s) only, not the American Chemical Society, ILPI, Safety Emporium, or any other party. Use of any information on this page is at the reader's own risk. Unauthorized reproduction of these materials is prohibited. Send questions/comments about the archive to secretary@dchas.org.